Latest News   | No more hunting around the shop to match up fire grilles with  faceplates - we've done it for you.  |  If you just want faceplates follow this link -  fire vent faceplates.

Fire Rated Sealant - (intumescent mastic)

Fire Rated Sealant  | Intumescent Mastic

Our Price: £2.24
Price Excludes VAT


Colour

Pack Size

 

Intumescent Mastic Features:

Tested to BS & EN Standard

Up to 4 hours fire rating

Acoustic Insulation Rated

Certifire Approval

Certifire Tested

Product Description:

Intuchem intumescent  mastic is a one part, fire rated, acrylic mastic with an acoustic rating. 

It is designed for sealing gaps around fire doors, window frames and for sealing joints, voids and irregular holes in fire rated compartmentation structures - maintaining their integrity when sealing around pipes and cables that penetrate through them.

The sealant has been independently tested (Certifire approved) in accordance with BS & EN Standards and can provide up to 4 hours fire rating depending on depth/width and volumetric area.

The sealant can be used on most construction substances, although we do recommend that a small area is tested on unusual substrates. It can be used in most low movement joints up to 25mm wide with no slump and can be overpainted.

AERATED CONCRETE / Acoustic performance:
Weighted Sound Reduction Index (RW) of up to 57db to BSEN ISO 140-3


AERATED CONCRETE Fire Performance

JOINT
GAP WIDTH MM
SEAL DEPTH MM
INSULATION
MINS
INTEGRITY MINS
HORIZONTAL
10
6
54
240
HORIZONTAL
20
20
UNCLASSIFIED
240
VERTICAL
10
6
UNCLASSIFIED
231
VERTICAL
12
12
UNCLASSIFIED
240
VERTICAL
15
10
40
240
VERTICAL
15
15
42
240
VERTICAL
20
15
49
240
VERTICAL
20
20
73
240
VERTICAL
35
20
92
240
VERTICAL
35
25
168
240

TIMBER Fire Performance

JOINT
GAP SURFACE
COMBINATION
GAP WIDTH MM
SEAL DEPTH MM
INSULATION MINS
INTEGRITY MINS
HORIZONTAL
HARDWOOD/ HARDWOOD
25
25
64
67
HORIZONTAL
HARDWOOD/ HARDWOOD
10
15
40
63
HORIZONTAL
SOFTWOOD/ SOFTWOOD
10
35
81
91
HORIZONTAL
SOFTWOOD/ SOFTWOOD
25
35
74
74
VERTICAL
HARDWOOD/ HARDWOOD
10
15
37
59
VERTICAL
HARDWOOD/ HARDWOOD
25
25
51
61
VERTICAL
SOFTWOOD/ SOFTWOOD
25
35
82
82
VERTICAL
SOFTWOOD/ SOFTWOOD
10
35
80
87


MIXED MATERIALS Fire Performance

JOINT
GAP SURFACE
COMBINATION
GAP WIDTH MM
SEAL DEPTH MM
INSULATION MINS
INTEGRITY MINS
HORIZONTAL
STEEL/ STEEL
25
25
40
240
HORIZONTAL
STEEL/ CONCRETE
25
25
48
240
HORIZONTAL
CONCRETE/ CONCRETE
30
25
48
240
HORIZONTAL
VERMICULITE/ AERATED CONCRETE
25
25
48
240
VERTICAL
STEEL/ STEEL
25
25
58
240
VERTICAL
STEEL/ CONCRETE
25
25
52
240
VERTICAL
CONCRETE/ CONCRETE
30
25
33
240
VERTICAL
VERMICULITE/ AERATED CONCRETE
25
25
58
240